Site: Lumen Cleveland (4000 Chester)
Company: Lumen Technologies
Metro: Cleveland
State: Ohio
Country: United States
Region: North America
Region: Americas
Address: Gross SqFt: 3,500
Total Power: 0.6 Megawatts
Power:
- Utility: The Illuminating Company
- Power densities: 125 watts/square foot
- AC and DC power options available
- Critical Power Capacity: Up to 600 kilowatts of critical load capability, isolated 2N UPS configuration delivered through independent 1600 amp buses. All UPSs are double conversion units in 2N architecture providing separated and isolated A and B power paths to critical loads
- UPS Energy Storage: Battery energy storage system
- Emergency Power: One 1MW diesel generator with stand-by generator connection for second generator. Unit housed in enclosure for protection with physical separation between unit and switchgear
- Fuel Storage: 36-plus hours of fuel in 2,000-gallon main fuel tank. Onsite refueling capable while running
Location:
- Campus: Two-story building
- Parking: 25-plus stalls
- Shipping: Street-level loading dock
- Access: Facility accessible to customers 24/7
- Flood Plain: Outside 100-year flood plain
- Seismic: Meets 1997 UBC Zone 1 standards
- Nearest Airport: Cleveland Hopkins International
- Storage: Secure storage room available for customer use