DataVita Glasgow

1 York Rd

░░░░░░ Login to view SqFt Gross Colocation Size

░░░ Contact Us to subscribe to our data service MW Total Power

Show SqM

Operated by:

The Building:

Two loading bays and two 200kg lifts for equipment
Control room/bridge for each hall
Braced Sttel framed building
Warm roof construction, three layer ashphalt weatherproofing system on concrete slab
Dedicated tenant plant areas on roof
Landlord fire alarm to BS5839 Category L2/P1
48 Car Parking Spaces

Data Hall Layout

Each hall 1000m2 net, PDUs within hall, CCU's in plant corridor
800mm clear floor void (1200mm on upper floor)
4000mm internal height, data hall floor to soffit
No internal shear walls, bracing or load bearing walls, allowing maximum future felxibility
2 hour fire resistance to structural frame
Sustainable surface water drainage system
Data Hall Floor loading:-

  • Imposed loading 12kN/m2 over complete building footprint
  • Ceiling and services 2.4 kN/m2
  • Raised access floor 0.6kN/m2

DataHall Mechanical & Electrical Services

Modular fit out with plant dedicated to each hall
4kW/m2 with options to extend to 7 kW/m2 +
Tier IV electrical and Tier III mechanical
Tenant owned 11kV switchgear and transformers
Landlord generator for building services
Tenant owned generators and bulk fuel storage external to building
6 hour day tank plus bulk fuel storage for 72 hours operation
Modular static UPS arrangement up to 2400kVA to allow for load growth
10 minute battery autonomy on each UPS. Options for 15 minute autonomy
Dedicated battery room for efficient temperature management
10 No x 400A PDUs per stream/per hall (20 No. per hall)
All PDUs dual fed from separate streams
Overhead power and underfloor data strategy proposed
3 chillers per hall, operating 2 + 1
24 CCUs per hall, operating 18 + 6, all electricity dual fed
Resilient pipework distribution design allowing partial isolation whilst retaining full operation
Free cooling incorporated within chilled water plant design
Options for chilled water connections to meet high density cooling application
Inverter driven pumps
Options for hot or cold aisle containment
10% of floor tiles provided as grilles
Possibility of fresh air cooling to 2 halls on upper floor
Leak detection
Automatic Fire Detection to BS5839 and BS6266
Gas suppression solution to halls, with tenant bottle storage areas
High sensitivity aspirating smoke detection in hall
Options for hi-fog/sprinklers to plant areas
BMS and SCADA system control and measurement
Full access control and security system, including CCTV and biometric readers
Options for Low and Zero Carbon technologies

Map and Nearby Locations:

1 York Rd
Click Map to begin Search

Sites within 15 miles of DataVita Glasgow

Show SqM
Distance Site About
11.89 miles Level3 Glasgow
12.90 miles iomart DC1 Glasgow

DataVita Glasgow Data Center Photos


The Front Entrance of the Fortis Data Centre
Source: Fortis

Operating Company

1 Facilities Owned
1 Markets Served
4.0 Megawatts
View Company

News

Read More News