PROPERTY
- Land Parcel: 1.15 acres
- Building Size: +/-300,500 sq.ft.
Transportation:
- Chicago O’Hare International Airport (ORD) - 18 miles Chicago
- Midway International Airport (MDW)- 10 miles
BUILDING DESCRIPTION
- Building Name: Chicago Byte Exchange Data Center (CBE1)
- Utility Power Feeds: Capacity 33 MW via seven (7) diverse routed
- utility service feeds
- Parking: 300+ spaces
- Number of Stories: Six (6) + Basement
- Loading Docks: Three (3) Spaces
DATA HALL SPECIFICATIONS
- Number of Data Halls: Three (3) expandable
- Data Hall 1: 30,000 sq.ft.
- Data Hall 2: 21,000 sq.ft.
- Data Hall 3: 22,000 sq.ft.
- Clear Height: 15’ to 32 ft.
DATACENTER AREA DESCRIPTION
- Raised Floor Area: 100,000+ sq.ft.
- Number of Data Halls: Three (3)
- Raised Floor Height: 36 in.
- Slab to Slab: 18 - 46 ft.
SECURITY
- Entrances: 24/7 Security Controlled
- Security Guards: Staffed 24/7/365
- Access Controls: Card key, three factor authentication and biometric readers
- CCTV: 24/7 surveillance of interior and exterior of facility
TECHNICAL OFFICE SPACE
- Staging: 950 sq.ft.
- Shared: 12 internal workstations
- Dedicated: 20,000+ sq. ft.
CRITICAL POWER
- Total Megawatts: 22 MW expandable
- Redundancy: Configured as N+1 or adjustable to tenant needs
- UPS SYSTEMS
- Description: UPS blocks are 6 to make 5 (6N/5) distributed redundant
- Redundancy: N+1
GENERATORS
- Description: 36 MW - fifteen (15) 2.4 MW units
- Redundancy: N+1
ON-SITE FUEL CAPACITY
- Storage Tanks: 60,000 gallons – expandable, 24 – 72 hours Full Load
- resiliency
HVAC SYSTEMS
- Description: ASHRAE A1 / ASHRAE W32
- Chillers: 900 Ton Centrifugal Units with Variable Frequency Drives
- Redundancy: N+1
- Water Cooling Units: 1400 Ton with Variable Frequency Drives
- Air Distribution System: 30 - 60 Ton CRAH Units
- Water Cooled Distribution: Rear Door Heat Exchangers and Direct-toChip cooling with dedicated secondary loops for CDUs (rack/facility)
- Dehumidification: Room-based with monitoring to meet Tenant needs
- PDU/RPP
- PDU Description: 500 - 650 kVA (480v/415v/208v)
- RPP description: Panel Whips or overhead busway with BCMS
FIRE PROTECTIONS
- Fire Alarm System Type: A microprocessor based intelligent
- addressable fire alarm system.
- Pre-Action System: Double interlock pre-action system
- Wet Sprinkler System: Administrative spaces, office spaces, corridors
- and other non-critical back of house spaces
NETWORK
- POE Conduits: Two diverse building entry points
- Meet-Me-Rooms: Two (2)
- Onsite Carriers: Eight (8) carriers including Zayo, ATT, Verizon,
- Lumen, Comcast with many others nearby.
- Carrier Hotel Proximity: Latency time to Cermak is 0.5 ms roundtrip
- with dark fiber and other low latency transport services available
CERTIFICATIONS (Planned)
- SSAE 16 Type II
- PCI-DSS
- ISO 27001
- ITIL
- Energy Star